PowerPro PowerCentre
Three Phase Input & Output Online Double Conversion UPS
Professional Power Protection
Features:
• Adaptive control dual mode technology
• Rectifier ‘Soft Start’ control
• Intelligent battery monitoring
• Powerful multiprocessor based design
• Parallel capability
• High reliability with low maintenance
• Sophisticated control and monitoring panel
• Automatic and manual static bypass
• Robust transistorised inverter
20
Technical Specification
Model PPC200 PPC250 PPC300 PPC400 PPC500 PPC600 PPC800
Power Rating kVA/kW 200/160 250/200 300/240 400/320 500/400 600/480 800/640
Power Factor 0.8
Input
Voltage 230/400 VAC 3 phase 4 wires + ground
Tolerance +15% -20%
Input Frequency 50Hz +/- 10%
Max RFI EN50091-2 Class A
Output
Voltage 230/400 VAC 3 phase, 4 wires + ground
Voltage Stability Static (balanced load) +/-1%, Static (unbalanced load) +/-1%, Dynamic (stop load 0-100%) +/-5%
Voltage Recovery Time 10ms
Frequency 50Hz
Frequency Tolerance +/-2,3,4 or 5% selectable, Free running +/-0.01%
Efficiency at 100% Load 95%
Crest Factor 3:1
Short Circuit Protection Electronic short circuit protection
Overload Capacity 110% for 60mins, 125% for 10mins, 150% for 60sec
Total Harmonic Distortion (THD) Linear +/-<1%, Non linear +/-<5%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of Cells 192 volts
Float Charging Voltage 428 volts adjustable
Boost Charging Voltage 436 volts adjustable
End of Discharge 320 volts
Battery Ambient Temperature 20° C to 25° C
Battery Test Automatic
General
Serial Communication Dry contacts plus RS232
Protection Degree IP20
Operating Temperature 0° C to 40° C
Storage Temperature -10° C to 50° C
Humidity <90% at 20° C (non condensing)
Altitude Power Derating Over 1000m use 5% each 1000m
Ventilation Forced air cooling
Acoustic Noise at 1m distance 65dBA 78dBA
Weight (kgs) 2100 2500 2800 3000 4500 5000 7000
Dimensions (mm) w x d x h 1500x900x1800 2360x900x1800 2920x900x1800 3880x900x1800 4780x900x1800