Features:
• Designed to the latest European EN 50171 Specification for Emergency
Lighting
• True double conversion and PWM technology
• Inverter stage output galvanic isolation transformer included
• Up to 91% efficiency
• Capable of 120% continuous overload to meet European Emergency
Lighting regulations
• Parallel mode operation (optional) (hot standby, redundant, symmetric
parallel)
• Large charger for faster recharge of batteries
• Maintenance bypass (for complete isolation of the inverter during
maintenance)
• Unique inverter design to suit high inrush lighting loads
• Bypass to load (changeover mode) user selectable
• LCD panel providing accurate detailed information about load,
batteries and inverter with advanced diagnostics
• RS232 and dry contacts for communication and remote monitoring
PowerPro EL 100 Series
Single Phase Input & Output Online Static Inverter
High Performance Static Inverter
21
Model EL104 EL105 EL106 EL108 EL110 EL112
Power Rating kVA/kW 4 / 3.2 5 / 4 6 / 4.8 8 / 6.4 10/8 12.5 / 10
Power Factor 0.8
Input
Voltage / Tolerance 230 VAC single phase, +/- 15%
By-pass Voltage 230 VAC single phase
Input Frequency 50Hz +/- 5%
Max RFI EN50091-2 Class A
Output
Voltage 230 VAC single phase
Voltage Stability Static (balanced load) +/-1%, Static (unbalanced load) +/-2%, Dynamic (step load 0-100%) +/-5%
Voltage Recovery Time After step load 0-100% max. 20ms
Frequency 50Hz
Frequency Tolerance Line synchronised +/- 1% / free running +/- 0.2%
Efficiency at 100% Load >87-91%
Crest Factor 3:1
Short Circuit Protection Electronic short circuit
Overload Capacity 120% continuous, 150% load 10min. 180% 1min, 200% for 1 sec
Total Harmonic Distortion (THD) Linear Load <3% / non linear load (75%NP and CF 3:1) <5%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 16 18 20
Float Charging Voltage 216Vdc 243Vdc 270Vdc
End of Discharge Voltage 160Vdc 180Vdc 200Vdc
Battery Ambient Temperature 25°C
Battery Protection Circuit breaker
Battery Test Automatic battery test once a week
General
Serial Communication Dry contacts plus RS232
Software T-Mon standard / SNMP module optional
Protection Degree IP41
Ambient Operating Temperature / Altitude 0°C to 40°C / <1000m (above sea level)
Standard Emergency Lighting EN 50171
Ventilation Forced air cooling
Acoustic Noise at 1m distance <56 dbA
Weight (kgs) 85 95 110 125 150 155
Dimensions (mm) w x d x h 300x500x1220
Technical Specification
The British Power Conversion Company
Comentários a estes Manuais